HAOMAI ELECTRIC TEST EQUIPMENT CO.,LTD

You test us, We test equipment!

Manufacturer from China
Active Member
4 Years
Home / Products / Protection Relay Test Set /

4x120V Three Phase Relay Test Kit Ultralight 3x40A For Power Plants

Contact Now
HAOMAI ELECTRIC TEST EQUIPMENT CO.,LTD
City:shenzhen
Country/Region:china
Contact Person:MrWilliam Wang
Contact Now

4x120V Three Phase Relay Test Kit Ultralight 3x40A For Power Plants

Ask Latest Price
Video Channel
Brand Name :HAOMAI
Model Number :HME-702
Certification :ISO9001:2015, Calibration Report
Place of Origin :China
MOQ :1 set
Price :negotiation
Payment Terms :T/T
Supply Ability :400 sets per month
Delivery Time :5-10 working days
Packaging Details :Transport Case + Carton
Product name :Relay Tester, Relay Test Kit, Secondary Injection Test Set
Current output :3x0…40A
Voltage output :4x0…120V
Output accuracy :≤0.2% for AC output
Auxiliary DC Output :110V/220V(max.1.5A)
Operation :local mode + PC mode
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Basic Three-phase Protection Relay Test Set

Model: HME-702

The HME-702 is a basic and economical protection relay test set with three-phase current outputs and four-phase voltage outputs. The HME-702 kit can apply to the testing not only on operating value and operating time of AC/DC relays, but also on complex voltage blocking directional over-current, zero sequence over-current, low-frequency load shedding and other protection functions of low voltage micro-processor based protection and whole group transmission of high voltage micro-processor based protection, and on starting value, quick-break value, harmonic blocking value and micro-processor based transformer differential protection.

The Basic Three-phase Protection Relay Test Set HME-702 has dual operation mode. It can be operated in local mode without PC, also can be controlled by software running on a PC after connecting to PC via communication cable.

Main Features

1) 3-phase current(3×40A) + 4-phase voltage(4×120V) output

2) Both local test and PC remote test available

3) Convenient operation in local mode

4) New high-fidelity linear power amplifier

5) Abundant binary inputs and binary outputs

6) Independent Aux. DC output

7) Perfect self-protection function

Technical Data

Current Generator

Setting range 3-phase AC(L-N) 3x0…40A
1-phase AC(LL-LN) 1x0…120A
DC(L-N) 3x…±10A
  3-phase AC(L-N) 3x420VA at 40A
Power 1-phase AC(LL-LN) 1x900VA at 120A
  DC(L-N) 3x120VA at 10A
Accuracy AC: ≤0.2%
DC: ≤0.5%

Voltage Generator

Setting range 4-phase AC(L-N) 4x0…120V
1-phase AC(L-L) 1x0…240V
DC(L-N) 3x…±160V
Power 4-phase AC(L-N) 4x80VA at 120V
1-phase AC(L-L) 1x100VA at 240V
DC(L-N) 3x70VA at 160V
Accuracy AC: ≤0.2%
DC: ≤0.5%

Auxiliary DC Supply

Voltage range 110V/220V(max.1.5A)
Power max.165VA/330VA

Binary Inputs

Number 8
Input characteristics idle contact or potential-free contact
Threshold characteristics “0”:0~6V; “1”:11V~250V
Max. measuring time 0.1ms~9999s
Time accuracy 0.1ms

Binary Outputs

Number 4
Type idle contact
Break capacity 220VAC/0.5A, 220VDC/0.2A

General Generators

Frequency range: 0~1000Hz(PC mode), 20~300Hz(local mode)
accuracy:<10mHz(0~450Hz),<20mHz(450~1000Hz)
resolution: 0.01Hz
Phase range: 0~360°
accuracy: 0.2°
resolution: 0.1°
Harmonic superposition orders: 1~20(PC mode), 1~6(local mode),
distortion: ≤0.5%

Power Supply

Nominal input voltage AC 220V/230V±10%, 1-phase
Nominal frequency 50/60 Hz
Rated current 10A at 230V
Connection standard AC socket (IEC 60320)

Miscellaneous

Weight 22kg(48.50 lb)
Dimensions (W x H x D, without handle) 400×300×180mm(15.75x11.81x7.09 in)
Connection port for PC connection

The Basic Three-phase Protection Relay Test Set HME-702 is the ideal basic relay testing device for all power facilities, power plants, relay manufactures, panel manufactures, research institutes, universities, and testing companies etc.

Inquiry Cart 0